Troubleshooting 30 
Condition 
Power On 
LED 
(green) 
On Battery 
LED 
(yellow) 
Overload 
LED 
(red) 
General 
Alarm LED 
(red) 
Audible alarm 
Can alarm 
be silenced 
("
On battery—No 
utility power 
Off On  Off Off  On— 4 second 
beep 
Yes 
On battery—Battery 
voltage condition 
Flashing Off 
Off 
Flashing  On—Continuous Yes 
On battery—
Overload condition 
Off On  On Off  On—1 second 
beep 
No 
On battery—Output 
voltage is out of 
range 
Off Flashing 
Off Flashing 
On—Continuous 
No 
On battery—Output 
wave is abnormal 
Flashing Flashing  Off 
Flashing  On—Continuous No 
 
For the location of individual LEDs, see "UPS front panel LED indicators (on page 
)." 
 
UPS does not start 
Action: 
1.
 
Be sure that the power cord is plugged in to a utility power receptacle. 
2.
 
Check the power source at the utility power receptacle. 
3.
 
Allow the UPS batteries to charge for 24 hours. 
 
UPS operates on battery only 
Action:   
1.
 
Save your work. 
2.
 
Power down the load devices connected to the UPS output receptacles. 
3.
 
Remove one or more load devices to reduce the power requirements. 
4.
 
Be sure the UPS configuration matches the utility voltage. Refer to "Selecting the UPS voltage 
configuration (on page 
).
 
UPS frequently switches between utility and battery power 
Action
1.
 
Check the input voltage and reconfigure the UPS ("
2.
 
Contact a qualified electrician to verify that the utility power is suitable for the UPS. 
 
UPS does not provide the expected backup time 