Specifications 33 
Power protection specifications 
     
UPS model 
VA 
Nominal power rating 
(W) 
Nominal voltage setting 
R1500 G2 NA 
1440 
1000 
110, 120 
R1500 G2 JPN/TWN 
1200 
900 
100 
 
1440 1000 
110 
R1500 G2 INTL 
1500 
1000 
220, 230, 240 
 
 
Voltage specifications 
    
Configuration setting (VAC) 
Available nominal output voltage (VAC) 
100 100 
110 110 
120 120 
220 220 
230 230 
240 240 
 
 
Output tolerance specifications 
    
Source of power 
Regulation 
Utility power (nominal 
range) 
-10% to +6% of nominal output voltage rating (within 
the guidelines of the Computer Business Equipment 
Manufacturers Association) 
Battery power 
±20% of nominal output voltage rating 
 
 
Output feature specifications 
    
Feature Specification 
Online efficiency 
95% nominal input voltage 
Voltage wave shape 
Sine wave; 5% THD with typical PFC load 
Surge suppression 
ANSI C62.41 Category A (formerly IEEE 587) 
Noise filtering 
Full-time EMI/RFI filtering 
 
 
Battery specifications 
        
Feature Specification 
Type 
6 V, 9 AH, sealed, maintenance-free, valve-regulated, 
rechargeable, lead-acid battery. 
Voltage 
The battery modules have a battery string voltage of 36 V. 
Charging 
Advanced charging for faster recovery. Complete charge takes no 
more than 24 hours. After approximately 4 hours, the batteries 
reach 90% charge at default nominal utility voltage and no load.