Installation  11 
 
Circuit overloading—Consideration should be given to the connection of the equipment to the supply 
circuit and the effect that overloading of the circuits might have on overcurrent protection and supply 
wiring. Appropriate consideration of equipment nameplate ratings should be used when addressing 
this concern. 
 
Reliable earthing—Reliable earthing of rack-mounted equipment should be maintained. Particular 
attention should be given to supply connections other than direct connections to the branch circuit, such 
as the use of power strips. 
 
Electrical requirements—All models require a dedicated (unshared) branch circuit, suitably rated for the 
specific UPS as stated in "Input specifications ("
" on page 
)" . 
 
Readying the equipment 
1. 
Check the battery recharge date specified on the label that is affixed to the shipping carton. 
  
 
IMPORTANT:
  Do not use the battery if the recharge date has passed. If the date on the battery 
recharge date label has passed without the battery being recharged, contact an HP authorized 
service representative for directions. 
  
2. 
Transport the packaged unit to its installation location. 
3. 
Unpack the equipment near the rack where the unit will be assembled. 
  
 
CAUTION:
  Always plan the rack installation so that the heaviest item is on the bottom of the rack. 
Install the heaviest item first, and continue to populate the rack from the bottom to the top. 
  
 
Installing the UPS 
Before installing the unit, review and adhere to all warnings provided in "Precautions (on page 
)." 
  
 
WARNING:
  A risk of personal injury or damage to the equipment exists. Uneven loading of 
equipment in the rack might cause the rack to become unstable. Install the heavier components 
first, and then continue to populate the rack from the bottom to the top. 
  
1. 
Install the mounting rails.