Installation  14 
Selecting the UPS voltage configuration 
Using a small tool, position the DIP switches according to the desired voltage configuration. 
 
  
 
NOTE:
  An asterisk (*) indicates the default setting. 
   
    
 
Output voltage 
Input voltage range 
DIP switch 1 
DIP switch 2 
R1500 G3 JPN/TWN  100 V* 
90–106 V 
Down 
Down 
 
110 V 
99–116 V 
Down 
Up 
R1500 G3 NA 
110 V 
99–116 V 
Down 
Up 
 
120 V* 
108–127 V 
Up 
N/A 
R1500 G3 INTL 
220 V 
198–233 V 
Down 
Up 
 
230 V* 
207–243 V 
Up 
N/A 
 
240 V 
216–254 V 
Down 
Down 
 
 
Connecting the host computer 
  
 
CAUTION:
  Only one communications port can be connected to the host computer. Connecting 
more than one will result in unexpected UPS behavior. If an option card is installed, the serial and 
USB communications ports are automatically disabled. 
  
Connect the UPS to a host computer using either the USB cable or the DB9 serial cable included with the UPS. 
Install HP Power Protector on the host computer. See the HP website 
(
) to download the latest version of HP Power Protector. 
  
 
NOTE:
  To install and configure the software, see the software user guide. The software user 
guide is available for download from the HP website (
). 
  
 
Connecting the serial communications port 
  
 
CAUTION:
  Use only the computer interface cable supplied with the UPS to connect the 
communications port to the host computer.