Troubleshooting  44 
Troubleshooting 
Alarm troubleshooting 
This UPS is designed for durable, automatic operation and also to alert you whenever potential operating 
problems might occur. Usually the alarms shown on the control panel do not mean that the output power is 
affected. Instead, they are preventive alarms intended to alert you of a possible condition. 
The following table describes typical alarms and conditions. If an alarm appears with a service code, contact 
HP technical support ("
on page 
on page 
).  
To check the Event Log for a list of active alarms: 
1. 
Press the ESC button on the front panel display to activate the menu options. 
2. 
Press the down arrow button until the Event Log menu appears. 
3. 
Press the Enter button to display the list of alarms and conditions. 
     
Alarm number  Alarm name 
Alarm description 
Alarm type 
Inverter AC Under Voltage  The UPS has detected abnormally low output voltage 
levels. 
Alarm 
Input AC Over Voltage 
The utility RMS voltage is greater than the maximum 
valid utility threshold. 
Alarm 
Input AC Under Voltage 
The utility RMS voltage is less than the minimum valid 
utility threshold. 
Notice 
Input Under/Over 
Frequency 
The utility frequency is out of usable frequency range.  Notice 
12 
Remote Emergency Power 
Off 
The external contacts in the rear of the UPS are 
configured for REPO operation and they have been 
activated. 
Alarm 
25 
Output Overload 
Load levels are at, or have exceeded, the 
configurable threshold limit for a Level 1 Overload 
condition. 
Notice 
26 
Rectifier Input Over Current  The UPS has detected that rectifier input current limits 
have been exceeded. 
Alarm 
27 
Inverter Output Over Current  The UPS has detected that inverter output current limits 
have been exceeded. 
Alarm 
28 
DC Link Over Voltage 
Indicates the link or rail voltage UPS has exceeded its 
upper threshold limit. 
Alarm 
31 
Inverter Fault 
The UPS has detected a fault in the inverter circuit 
while attempting recovery from bypass or Fault 
modes. 
Alarm 
55 
Shutdown Imminent 
Indicates that the UPS entered a state where it might 
stop operating abruptly without notice. An alarm is 
issued when the BTR reaches 0 at the end of a battery 
discharge cycle after all connected devices should 
have shutdown gracefully already. 
Alarm 
56 
Low Battery Warning   
Warning alarm indicating battery remain or battery 
time remaining is lower than the battery low warning 
level defined for the UPS. 
Alarm