HP (Hewlett-Packard) R5000 ユーザーズマニュアル

ページ / 62
 
Specifications  52 
Feature 
Specification 
Surge suppression 
High-energy 6500 A peak 
Noise filtering 
MOVs and line filter for normal and common mode 
use 
 
 
Battery specifications 
   
Feature 
Specification 
Type 
Each model contains maintenance-free, sealed, valve 
regulated lead-acid batteries with an 8-year minimum float 
service life at 25°C (77°F). 
Voltage 
The battery modules have a battery string voltage of 216 V. 
Charging 
Complete charge takes no more than 48 hours. 
Approximately 3 hours to 80 percent capacity at default 
nominal utility voltage and no load. 
 
 
Average battery runtime 
Average battery runtimes are approximate and vary depending on connected equipment, configuration, 
battery age, temperature, and so on. These estimates are based on the batteries at beginning of life. 
     
Load % 
Estimated 
battery runtime 
(minutes) 
Runtime with 
one ERM 
(minutes) 
Runtime with 
four ERMs 
(minutes)* 
20 
44 
123 
436 
50 
16 
44 
145 
80 
25 
83 
100 
5.7 
20 
64 
 
* NA/JPN model only 
 
Minimum battery runtime 
Minimum battery runtimes are at beginning of life. 
     
Load % 
Internal battery 
runtime 
(minutes) 
Runtime with 
one ERM 
(minutes) 
Runtime with 
four ERMs 
(minutes)* 
20 
36 
100 
360 
50 
12 
36 
115 
80 
23 
80 
100 
18 
58 
 