HP (Hewlett-Packard) 6205B ユーザーズマニュアル
5-47 To check the output stability, proceed as
a.
Connect test setup shown
b. Turn CURRENT controls
clockwise
and adjust VOLTAGE controls for 40Vdc output.
c .
Allow 30 minutes warm-up then record
the differential voltmeter indication.
d.
8 hours, differential voltmeter
change by less than
from indication
recorded in Step c.
5-48 TROUBLESHOOTING
5-49 Before attempting to troubleshoot this in-
strument, ensure that the
is with the instru-
ment and not with an associated circuit. The per-
formance test (Paragraph 5-10) enables this to be
determined without having to remove the instru-
ment from the cabinet.
formance test (Paragraph 5-10) enables this to be
determined without having to remove the instru-
ment from the cabinet.
5-50 A
understanding of the principles of
operation is a helpful aid
troubleshooting, and
before attempting to troubleshoot
the unit in detail. Once the principles of opera-
tion are understood, refer to the overall trouble-
tion are understood, refer to the overall trouble-
the symptom and probable cause.
5-51 The schematic diagram at the rear of the
manual (Figure 7-1) contains normal voltage
TM 11-6625-2965-14&P
ings taken at various points within the circuits.
These voltages are positioned adjacent to the ap-
plicable test points (identified by encircled num-
These voltages are positioned adjacent to the ap-
plicable test points (identified by encircled num-
bers). Component and test point designations are
marked directly on the main printed wiring board.
marked directly on the main printed wiring board.
5-52
a defective component is located, replace
it and re-conduct the performance test. When a
component is replaced, refer to the repair and re-
placements and adjustment and calibration para-
graphs in this section.
graphs in this section.
5-53 OVERALL TROUBLESHOOTING PROCEDURE
5-54 To locate the cause of trouble
Steps
1, 2, and 3 in sequence.
(1) Check for obvious troubles such as
open fuse, defective power cord, input power fail-
ure, or defective voltage or current meter. Next
remove the top cover (held by four retaining
ure, or defective voltage or current meter. Next
remove the top cover (held by four retaining
screws) and inspect for open connections, char-
red components, etc.
red components, etc.
If the trouble source cannot
be detected by visual inspection, proceed with
Step 2.
Step 2.
(2) In almost
cases, the trouble can be
caused by improper dc bias or reference voltages;
thus, it is a good practice to check voltages in
Table 5-2, before proceeding with Step 3.
thus, it is a good practice to check voltages in
Table 5-2, before proceeding with Step 3.
(3) Disconnect the
Table 5-2.
Reference Circuit Troubleshooting
METER
METER
NORMAL
NORMAL
STEP
COMMON
POSITIVE
INDICATION
RIPPLE
IF INDICATION ABNORMAL, TAKE THIS ACTION
(P-P)
1
+s
33
6.2 0.3Vdc
.
Check 12.4 Volt bias or VR1 (See next paragraph)
2
31
+s
6.2
.
Check 12.4 Volt bias or VR2 (See next paragraph)
3
+s
37
12.4 *1.
Check Q8, Q9,
CR23, C1O,
4
38
41
7.5 .7Vdc
Check C12, CR8, CR24, CR25
Table 5-3.
Overall Trouble shooting
SYMPTOM
CHECKS AND PROBABLE CAUSES
High output voltage
a.
Front
meter defective.
output voltage
a .
Fuses blown (Check
or C14 for short).
5-9