HARDWARE 
 
28 
CIO Remote CAN Digital I/O Module 
  GEK-106465A 
 
INTERNAL STATE 
V 52/a 
V 52/b 
SUPERVISION 
52 open 
ON 
ON 
OK 
52 closed 
ON 
OFF 
OK 
TRIP 
OFF 
OFF 
Ok if t < 0.5 s 
TRIP with 52 open 
OFF 
ON 
OK 
 
 
Status of Involved Elements 
Inputs to F650 
Decision 
CIRCUIT 
STATUS 
OUTPUT 
STATUS 
(F35-F36) 
BREAKER 
STATUS 
OPERAND 
CONTACT 
INPUT_00_10 
 (Va_COIL2) 
V 52/a (15-16) 
OPERAND 
CONTACT 
INPUT_00_11 
 (Vb_COIL2) 
V 52/b (17-18) 
OPERAND 
CONTACT 
INPUT_00_15 
(SUP_COIL2) 
Healthy Open 
52 
closed 
ON 
OFF 
ON 
Healthy Open 
52 
open 
ON 
ON 
ON 
Healthy Closed 
52 
closed 
OFF 
OFF 
ON (if t < 500 ms) 
OFF (if t > 500 ms) 
Healthy Closed 
52 
open 
OFF 
ON 
ON (if t < 500 ms) 
OFF (if t > 500 ms) 
Defective 
Open 
52 closed 
OFF 
OFF 
OFF (500 ms delay) 
Defective 
Open 
52 open 
OFF 
OFF 
OFF (500 ms delay) 
Defective 
Closed 
52 closed 
OFF 
OFF 
OFF (500 ms delay) 
Defective 
Closed 
52 open 
OFF 
OFF 
OFF (500 ms delay) 
 
There is a possibility to monitor the trip circuit continuity not only via its auxiliary contact 52/a, but also with auxiliary 
contact 52/b. This avoids the need to install a resistance in parallel with auxiliary 52/a. The correct connection is 
shown on FIGURE 3-12. 
The circuit works in a similar way to the one described in the previous section, but it uses both supervision inputs 15-
16 and 17-18. 
The advantage in this case is that circuit supervision with 52 open is more complete, as input V 52/b is used through 
contact 52/b, (that is closed when the breaker is open). 
We must point out that in this scheme, the tripping contact, shown in the example as the CIO trip relay, can be the 
one in the relay (terminals 35 and 36), or be provided by another protection or by the parallel of several protections. 
This provides high flexibility in the use of this circuit. 
The battery voltage can also be monitored, by using one of the standard digital inputs.