Hitachi L2002 ユーザーズマニュアル

ページ / 304
L200
2
 Inverter
xiii
Terminal Tightening Torque and Wire Size
The wire size range and tightening torque for field wiring terminals are presented in the 
tables below.   
Wire Connectors
WARNING: Field wiring connections must be 
made by a UL Listed and CSA Certified ring lug 
terminal connector sized for the wire gauge being 
used. The connector must be fixed using the 
crimping tool specified by the connector 
manufacturer.
Input 
Voltage
Motor Output
Inverter Model
Power Terminal 
Wiring Size 
Range (AWG)
Torque
kW
HP
ft-lbs
(N-m)
200V
0.2 1/4
L200-002NFE(F)2/NFU2
16
0.6
0.8
0.4
1/2
L200-004NFE(F)2/NFU2
0.55
3/4
L200-005NFE(F)2
0.75
1
L200-007NFE(F)2/NFU2
14
0.9
1.2
1.1
1 1/2
L200-011NFE(F)2
1.5
2
L200-015NFE(F)2/NFU2
12
2.2
3
L200-022NFE(F)2/NFU2
10
3.7
5
L200-037LFU2
12
5.5
7 1/2
L200-055LFU2
10
1.5
2.0
7.5
10
L200-075LFU2
8
400V
0.4
1/2
L200-004HFE(F)2/HFU2
16
0.9
1.2
0.75
1
L200-007HFE(F)2/HFU2
1.5
2
L200-015HFE(F)2/HFU2
2.2
3
L200-022HFE(F)2/HFU2
3.0
4
L200-030HFE(F)2
14
4.0
5
L200-040HFE(F)2/HFU2
5.5
7 1/2
L200-055HFE(F)2/HFU2
12
1.5
2.0
7.5
10
L200-075HFE(F)2/HFU2
Terminal Connector
Wiring Size 
Range (AWG)
Torque
ft-lbs
(N-m)
Logic/Analog connector
30—16
0.16—0.19
0.22—0.25
Relay connector
30—14
0.37—0.44
0.5—0.6
Cable
Terminal (ring lug)
Cable support