Operation – Navigation
990-2359A
Smart-UPS® VT 10-30kVA, 200/208V and XR Battery Enclosure Operation Guide 
9
Switch load OFF (disconnect the UPS output to the load equipment): 
• From the Main Menu, select Control and press ENTER
• Use UP/DOWN key to navigate to Turn Load Off, and press ENTER
• Select YESTurn Load Off
Switch load ON: 
• From the Main Menu, select Control and press ENTER
• Use UP/DOWN key to navigate to Turn Load On, and press ENTER
• Select YES, Turn Load On
Switch into bypass: 
• From the Main Menu, select Control and press ENTER
• Use UP/DOWN key to navigate to UPS into Bypass and press ENTER
• Use UP/DOWN key to navigate to YES, UPS into bypass, and press ENTER
Switch out of bypass: 
• From the Main Menu, select Control and press ENTER
• Select UPS out of Bypass and press ENTER
• Use UP/DOWN key to navigate to YESUPS out of Byp, and press ENTER
Status views
Select Status on the Main Menu to view the status on the following parameters
Voltage on all phases. 
Utility voltage (V), bypass voltage (V), and output voltage (V) for each phase.
Current on all phases. 
Utility current (A), bypass current (A), and output current (A) for each phase.
kVA and kW. 
Apparent power (kVA) and real power (kW) generated by the UPS to the load.
Control
Status
Setup
Logging
Display
Diags
Help
Main Menu