Smart-UPS® VT 10-30kVA, 200/208V and XR Battery Enclosure Operation Guide 
25
Mechanical Bypass
Mechanical Bypass Lever
For increased availability, the UPS is equipped with an internal mechanical bypass system providing 
mains power directly to the output, bypassing all UPS electronics. 
Turn into mechanical bypass
From the Main Menu, select Control and press ENTER
Use UP/DOWN key to navigate to UPS into Bypass and press ENTER
Use UP/DOWN key to navigate to YES, confirm UPS into bypass, and press ENTER
Remove UPS Front Panel
Start-up is included with the UPS, and the start-up procedure described here is only 
applicable if the UPS requires a subsequent start-up.
CAUTION!
The load is not protected by the UPS when the internal mechanical bypass system is 
active, and, the power is not conditioned. 
NOTE!
If the UPS is running and controllable through the display, carry out steps 1 through 6. 
If not, go directly to step 4. 