6  Commissioning 
Issue 10/06 
 
MICROMASTER 440 
46 
Operating Instructions (Compact) 
A high thermal motor load and when the line supply is frequently switched-
out/switched-in requires, for closed-loop vector control 
−  that a KTY84 sensor is used, or 
−  an external 24V power supply voltage is connected 
 
Motor cooling
 
(Selects motor cooling system used) 
  0  Self-cooled: Using shaft mounted fan attached to motor 
  1  Force-cooled: Using separately powered cooling fan 
 2  Self-cooled and internal fan 
  3  Force-cooled and internal fan 
 
Motor temperature sensor 
Selects the motor temperature sensor. 
 0  No sensor 
 1  PTC thermistor (PTC) 
 2  KTY84 
 
r0631
ADC
5 V
Signal
loss
detection
T
= 4 s
2
1
No sensor
PTC
KTY
0
P0604
Fault
F0015
&
P0601 = 2
Thermal
motor
model
r0633
r0632
r0035
1
Motor
temp.
reaction
P0610
P0601
Equivalent
circuit data
P
V,mot
Power dissipation
V
ϑ
0
1
0
1
r0052
Bit13
PTC
KTY
 
Alarm threshold, motor overtemperature 
Defines the alarm threshold for the motor overtemperature protection. This threshold, where 
either a shutdown (trip) or Imax reduction is initiated (P0610) always lies 10 % above the 
alarm threshold. 
ϑ
warn
 :
ϑ
trip
  
 
: Trip threshold (max. permissible temperature)
P0604
 
 
1.1
 
 
 
 
1.1
 
 
warn
trip
=
=
ϑ
ϑ
Warning threshold (P0604)
 
The alarm threshold should be at least 40 °C greater than the ambient temperature P0625.
P0604 
≥ P0625 + 40 °C
 
 
 
Inverter temperature reaction  
Defines reaction when motor temperature reaches warning threshold. 
  0  No reaction, warning only 
  1  Warning and I
max
 reduction (results in a lower output frequency) 
  2  Warning and trip (F0011) 
 
Motor overload factor [%] 
Defines motor overload current limit in [%] relative to p0305 (rated motor current). Limited to 
maximum inverter current or to 400 % of rated motor current (p0305), whichever is the 
lower. 
 
2
 
0
 
P0601 = ... 
P0604 = ... 
130.0 °C
P0610 = ... 
0
P0335 = ... 
P0640 = ... 
150.0 %