AEG 750 ユーザーズマニュアル

ページ / 54
35
operating stag has been reached (pos. 7 p. 3).
In  case  anything  different  occurs,  please 
follow the instructions in Chapters 6.2 / 6.3.
i
Please shut down the entire system if you cannot 
solve  any  problems  which  occur.  Please  contact 
our hotline (see page 4).
5.
When  the  LINE  MODE  display  is  lit,  switch 
on  your  loads  one  after  the  other.  Note  the 
maximum  permitted  UPS  load  when  doing
this (pos. 9 fig. p. 42).
In  particular,  bear  in  mind  the  considerable  power 
consumption  of  loads  such  as  laser  printers,  large  CRT 
monitors  and  the  like  which  can  quickly  lead  to  a  UPS 
overload.
5.4.2
Configuration
To  reconfigure  the  internal  UPS  setup  options,  follow  the 
procedure as below:
1.
Press the Configure 
 button more than three 
seconds. Then UPS will transfer from configure mode 
to “output voltage mode” showing the value by a 
flashing LED at 220 Vac, 230 Vac or 240 Vac.
2.
Press the Configure 
 button more than one 
second, the UPS allows you to select the “output 
voltage mode” one by one. 
3.
After selecting the mode, press the Enter 
 button
more than three seconds, the “output voltage mode”
is configured. 
4.
UPS will automatically transfer from configure mode 
to “operating mode” displayed by a flashing LED 
beside NORMAL, GENERATOR or WIDE RANGE.
5.
Press the Configure 
 button more than one 
second; the UPS will allow you to select the “operating 
mode” one by one.