Executing the Test:
To execute the manual check press the button 
 for 
about five seconds until the UPS acoustic signal fades 
out.
Additionally  the  button  has  the  function  to  deactivate 
the  acoustic  alarm  signal.  Press  the  button 
  when 
the acoustic alarm it audible for about 1 second.  The 
tone stops. Any new error that is reported by a signal 
activates the alarm signal again. 
Note: 
The  acoustic  signal  can  not  be  switched  off  in 
the following situations: 
Battery  weak,  overload,  fan  failure,  fan  error, 
time cutout, overheat.
If  the  monitoring  electronics  detect  an  irregularity  during  the 
procedure  described  above,  the  load  is immediately switched 
back onto the mains and is thus supplied with voltage. At the 
same  time,  an  acoustic  fault  signal  and  the  corresponding 
signals  from  LEDs  in  acc.  with  Chapter  6  "Signalling"  are 
output.
Faults  detected  and  signalled  during  diagnosis 
must  be  rectified;  otherwise  there  is  a  risk  of 
load voltage loss if a mains failure occurs!
5.6
Interfaces and communication
5.6.1
Data line protection RJ11 and RJ45 
(modem / telephone / fax / network)
The  incoming  data  lines  are  connected  to  the  “IN”  line  at  the 
rear of the UPS. The “OUT” line is connected via data line with 
your terminal.
i
The  data  line  protection  supports  networks  with 
transfer rates between 10 and 100 MBit/s.