Signalling and failure solution
6.1
LED display
1.
Main switch of the UPS (mains switch)
2.
Push button for manually triggering the system test or 
switching off the buzzer 
3.
Push button to view the configuration
4.
Acknowledgement button 
5.
INPUT TYPE: LED for preselected operation state
and output voltage
NORMAL: (Normal mode) The LED indicator will 
illuminate during normal mode, the UPS accepts AC 
input voltage range from +/-20%.
GENERATOR: (Generator mode) No change to 
voltage window. However, the low frequency transfer 
point is changed to 40Hz and there is no limitation for 
high frequency transfer point. 
WIDE RANGE: (Extended UPS) 
AC input voltage ranges from -30% / +20%.
6.
VOLTAGE RANGE: LED for current output rate 
voltage 220Vac / 230Vac (ex factory) / 240Vac.
7.
LINE  MODE:  Green  LED  for  power  mode.  The  line 
LED  indicator  illuminates  when  the  AC  source  is 
present.
8.
BAT. MODE: Yellow LED for battery mode. The LED 
indicator  will  flash  every  four  seconds  when  the  UPS