AEG PROTECT 1.11 ユーザーズマニュアル

ページ / 61
23
4.3
Set-Up
Note  the  following  points  when  setting  up  the  UPS  system 
and its external battery units (special accessories):
The contact surface must be smooth and level. It must 
also be sufficiently strong and sturdy to avoid vibration 
and shocks.
Make sure that the mounting is able to support the 
weight, especially in conjunction with external battery 
units (special accessories).
Set up the units so that adequate air circulation is 
assured. There must be at least 200 mm clearance 
behind the rear fans for ventilation purposes. Do not 
block the intake openings on the front and, if present, 
on the side of the unit. There must be a gap of at least 
50 mm here.
External battery units must be placed on the side of the 
UPS system. To ensure the greatest possible 
mechanical stability, do not place the external battery 
unit(s) above or below the UPS system.
Avoid extreme temperatures! We recommend an 
ambient temperature from 15°C to 25°C in order to 
maximize the service life of the batteries. Do not 
expose the units to direct sunlight or operate them 
close to other heat sources such as radiators.
Protect the units against external effects (in particular 
moisture and dust). In this regard, please also refer to 
the instructions in chapter 3, page 15 in these operating 
instructions.
If you transport the unit from a cold room into a warm one, or 
if  the  room  temperature  suddenly  drops,  then  condensation 
may  form  inside  the  unit.  To  avoid  any  damage  due  to 
condensation,  let  the  unit  acclimate  for  2  hours  before  you 
switch it on.