This  so-called  passive  redundancy  protects  against  the  total 
failure of the voltage supply on the secured busbar; however, 
in  this  operating  mode,  mains  faults  would  directly  affect  the 
load.  As  a  result,  the  electronics  continuously  attempt  to 
switch  back  to  "online"  /  normal  operating  mode  (e.g.  when 
the overload or overtemperature goes away).
The bypass consists of an inverse-parallel thyristor stack and 
functions  as  an  extremely  rapidly  switching  link  between  a 
load and the mains. The synchronization unit ensures that the 
frequency  and  phase  of  the  inverter  voltage  is  synchronized 
with  the  mains  and  can  therefore  be  switched  over  without 
interruption (within the tolerance limits).
i
The  bar  graph  LED  functions  as  the  display  of 
the UPS capacity utilisation. The acoustic signal 
sounds  every  2  seconds  during  this  operating 
mode.
6.1.4
Manual Bypass