2.2
System Description
The  UPS  is  connected  between  the  public  utility  mains  and 
the loads to be protected.
The power section  of the rectifier converts the mains  voltage  to 
DC  voltage  for  supplying  the  inverter.  The  circuit  technology 
used  (PFC)  enables  sinusoidal  current  consumption  and 
therefore  operation  with  little  system  disturbance.  A  separate, 
second rectifier (charging REC set up using switch mode power 
supply technology) is responsible for charging or trickle-charging 
the  battery  connected  in  the  intermediate  circuit.  The 
configuration of this charging REC means the harmonic content 
of  the  charging  current  for  the  battery  is  almost  zero,  which 
increases the service life of the battery even more. The inverter 
is  responsible  for  converting  the  DC  voltage  into  a  sinusoidal 
output  voltage.  A  microprocessor-driven  control  based  on  a 
pulse-width  modulation  (PWM)  guarantees,  in  conjunction  with 
digital  signal  processor  technology  and  extremely  fast  pulsating