AEG PROTECT B. 2000 ユーザーズマニュアル

ページ / 54
34
7.
Activate  the  external  EPO  switch  to  test  the 
EPO function
8.
De-activate  the  external  EPO  switch  and  restart 
the UPS.
5.4
Electric start-up
First  compare  the  setting  with  the  rated  voltage  valid  in  your 
country. The factory default setting is 230 V
Make  any  changes  in  accordance  with  the  description  in 
chapter 5.4.2 “Configuration”.
5.4.1
Connection
Now  connect  the  input  of  the  UPS  (pos. 1 fig. p. 24/25) to  the 
mains  connection  cable  provided  and  plug  the  mains 
connector into a suitable shockproof socket.
1.
Avoid 
using 
extension 
cables 
and/or 
adapters. In  particular  in  the  case  of  high-
capacity types, ensure that the fusing in your 
sub-distribution  is  adequately  dimensioned:
The PROTECT B. 3000 for example requires 
its own connection with a 16 A fuse. No other 
loads should be connected to this circuit!
2.
Then  connect  the  outputs  of  your  UPS  (pos. 
2  fig.  p.  24/25)  to  your  loads. Use  the  load 
connection  cables  provided  for  this.  Don’t 
switch  on  the  loads  yet.  Please  contact  your 
dealer  if  you  require  additional  load 
connection cables.
3.
Now  switch  on  the  UPS. To  do  this,  press 
and hold the UPS main switch  
 for about 3 
seconds until the display goes on. 
4.
The  UPS  acknowledges  your  command  by 
starting  a  self  test.  During  this  automatically
running  procedure  a  periodically  audible 
signal  can  be  heard  The green "Mains" LED  
is  permanently  illuminated  when  the  normal