Also avoid short-term unit overloads, which may, for example, 
occur  when  connecting  a  laser  printer  or  laser  fax  machine. 
Do not connect any household appliances to the UPS.
Never  connect  any  additional  loads  to  the  UPS 
if  there  is  a  mains  failure,  i.e.  if  the  UPS  is 
working in emergency power operation.
The UPS output is de-energised if there is an overload of 150 % 
for  longer  than  200  ms  during  normal  operation.  During 
emergency  power  operation,  an  instant  shutdown  additionally 
takes place if there is a unit overload of > 120 % (see Chapter 
3.4). As  a  rule,  if  there  has  never  been  an  overload  during 
normal  operation,  there  will  not  be  one  during  battery 
operation either.
5.5.4
System Diagnosis / Battery Test
It  is  possible  to  press  the  "TEST"  button 
(pos.  2  p.  42)  to
perform  a  manual  check  on  the  major  hardware  components 
of  the  UPS.  This  test  can  only  be  initiated  if  the  unit  is 
operating normally, and it involves switching the loads over to 
UPS  inverter  supply  for  a  few  seconds.  As  well  as  checking 
the  procedures  and  the  functional  capability  of  the  static 
bypass  switch,  this  check  also  involves  drawing  current  from 
the  battery  for  a  short  time.  The  inverter  has  to  provide  the 
entire  load  supply,  which  means  the  entire  process  chain  is 
tested with this function. Normal operation is restored after the 
check.