Description Adjustable 
parameters 
Presetting 
Auto bypass 
[enabled], [disabled] 
 
“enabled” means UPS will have 
bypass output when utility power on. 
“disabled” means UPS will not have 
bypass output when power on but 
could get bypass output when UPS is 
fault or overload. 
enabled 
Clear Event 
Log 
The number after “Total events” shows 
how many events are currently stored 
in the log. 
Press the “ENTER” button for one 
second to reset the event count to 
zero and clear the log. 
— 
LCD Contrast  [-5], [-4], …[-1], [0], [+1], …[+4], [+5] 
The LCD Contrast is adjustable and 
the valid range is from -5 to +5.  
Restore 
Factory 
Settings 
[no], [yes] 
Setting only available in UPS stand-by 
mode. 
Restoring the factory settings: 
z
 
Returns all user-configurable 
EEPROM settings to default 
factory settings 
z
 
Resets all pending on/off 
commands 
z
 
Clears the Event Log and resets 
all time stamps 
z
 
Resets the battery test status 
z
 
Initiates the Self Diagnostics test 
No 
i
 
The “Restore Factory Settings“ process is completed after
the UPS was switched off completely. Wait until the fans
stopped to allow the UPS internal EEPROM overwriting.