Nortel Networks P0607274 0 ユーザーズマニュアル

ページ / 32
Chapter 1  Uninterruptable Power Supply (UPS) Overview    19
UPS Installation and Configuration Guide
203200
Main intelligence module removed
Warn
200400
UPS runtime calibration cancelled
Info
203300
Main intelligence module failed
Error
200401
UPS runtime calibration cancelled 
by user
Info
1030
Minimum redundancy regained
Warn
200402
UPS runtime calibration aborted by 
power failure
Info
310700
Maximum internal UPS 
temperature exceeded
Warn
200403
UPS unable to perform runtime 
calibration: Capacity < 100 %
Warn
2030
Minimum redundancy lost
Warn
200700
UPS enabling SmartTrim
Info
100300
Normal power restored: UPS on 
line
Info
201301
UPS on bypass: user set via 
software or panel
Info
103700
Redundant intelligence module OK
Info
201302
UPS system is in maintenance 
bypass set by switch
Info
103800
Redundant intelligence module 
added
Info
203100
UPS module failed
Error
203400
Redundant intelligence module 
removed
Warn
301300
UPS internal temperature over limit Warn
203500
Redundant intelligence module 
failed
Warn
301301
UPS battery charger failure
Warn
203600
System level fan OK
Info
200007
UPS on battery: Large momentary 
spike
Warn
2001
System shutdown Complete
Info
301302
UPS on bypass: severe DC 
imbalance overload
Warn
2036
System level fan failed
Error
301303
UPS on bypass: output voltage 
outside limits
Warn
1006
Shutdown cancelled
Info
301304
UPS on bypass: top module fan 
needs repair
Error
1016
System Shutdown started
Info
300100
UPS output overload
Warn
100401
Scheduled UPS self-test passed
Info
300300
UPS battery is discharged
Warn
300201
Scheduled UPS self-test failed
Error
301600
UPS battery needs replacing
Error
300202
Scheduled UPS self-test failed: 
Invalid test
Warn
100402
User-initiated UPS self-test passed
Info
100403
Self-test at UPS passed
Info
100601
User-initiated shutdown cancelled
Info
300205
Self-test at UPS failed
Error
101601
User-initiated shutdown started
Info
300206
Self-test at UPS failed: Invalid test
Warn
300204
User-initiated self-test failed
Error
1018
Smart Cell signal restored
Info
300206
User-initiated self-test failed: Invalid 
test
Warn
Table 1   UPS Event messages
Event ID Event
Type
Event ID Event
Type