IBM UPS1500THV ユーザーズマニュアル

ページ / 68
 
   
9
 
 
 3:  U
SER 
C
ONFIGURABLE 
I
TEMS
 
N
OTE
:  S
ETTINGS ARE MADE THROUGH THE SUPPLIED 
P
OWER
C
HUTE SOFTWARE OR 
 
O
PTIONAL 
S
MART 
S
LOT ACCESSORY CARDS
.  R
EFER TO THE SOFTWARE HELP GUIDES FOR DETAILS
F
UNCTION
 
F
ACTORY
 
D
EFAULT
 
U
SER 
S
ELECTABLE 
C
HOICES
 
D
ESCRIPTION
 
Automatic Self-Test 
Every 14 days  
(336 hours) 
Every 14 days 
(336 hours), 
Every 7 days 
(168 hours), 
On Startup Only,  
No Self-Test 
This function sets the interval at which the 
uninterruptible power supply will execute a 
self-test.  
UPS ID 
UPS_IDEN 
Up to eight characters  
Use this field to uniquely identify the unin-
terruptible power supply, (i.e. server name 
or location) for network management pur-
poses. 
Date of Last Battery  
Replacement 
Manufacture Date 
mm/dd/yy 
Reset this date when you replace the battery 
module. 
Minimum Capacity 
Before Return from 
Shutdown 
0 percent 
0, 15, 30, 45, 50, 60, 75, 
90 percent 
The uninterruptible power supply will 
charge its batteries to the specified percent-
age before it powers up connected equip-
ment, following a low-battery shutdown. 
Alarm Control 
Enable 
Enable, Mute, Disable 
User can mute an ongoing alarm or disable 
all existing alarms permanently. 
Shutdown Delay 
90 seconds 
0, 90, 180, 270, 360, 
450, 540, 630 seconds 
The interval is set between the times when 
the uninterruptible power supply receives a 
shutdown command and actual shutdown. 
Synchronized Turn-on 
Delay 
0 seconds 
0, 60, 120, 180, 240, 
300, 360, 420 seconds 
The uninterruptible power supply will wait 
the specified time after the return of utility 
power before turn-on (to avoid branch cir-
cuit overload).  
Output Voltage 
750THV, 1000THV 
and 1500THV mod-
els: 
230VAC 
750THV, 1000THV and 
1500THV models: 
220, 230, 240VAC 
750THV, 1000THV and 1500THV models: 
Allows the user to select the output voltage. 
Voltage Sensitivity 
The uninterruptible 
power supply detects 
and reacts to line voltage 
distortions by transfer-
ring to battery operation 
to protect connected 
equipment. 
 High 
: Brightly illumi-
nated - high sensitivity. 
 
: Dimly illuminated 
medium sensitivity. 
  
 : No illumination; 
low sensitivity. 
Adjust by pressing the voltage sensitivity 
button 
  (rear panel). Use a pointed ob-
ject (such as a pen) to do so. 
Note: In situations of poor power quality, 
the uninterruptible power supply may fre-
quently transfer to battery operation. If the 
connected equipment can operate normally 
under such conditions, reduce the sensitivity 
setting to conserve battery capacity and 
service life. 
Low Battery Warning 
 
 2 minutes 
PowerChute software 
provides automatic, 
unattended shutdown 
when approximately 
two minutes of bat-
tery operated runtime 
remains. 
: Brightly illumi-
nated - low battery 
warning level of about 
two minutes
 
: Dimly illuminated 
- low battery warning 
level of about five min-
utes
  
 :  No illumination; 
low battery warning 
level is approximately 
eight minutes
Possible interval set-
tings: 2, 5, 8, 11, 14, 17, 
20, 23 minutes. 
The uninterruptible power supply will beep 
when two minutes of battery runtime re-
mains. 
Change the warning interval setting by 
pressing the voltage sensitivity button, while 
pressing and holding the 
 button. 
Change the low battery warning interval 
setting to the time that the operating system 
or system software requires to safely shut 
down.