IBM UPS750TLV ユーザーズマニュアル

ページ / 68
 
   
 10
 
 
 
N
OTE
:  S
ETTINGS ARE MADE THROUGH THE SUPPLIED 
P
OWER
C
HUTE SOFTWARE OR 
 
O
PTIONAL 
S
MART 
S
LOT ACCESSORY CARDS
.  R
EFER TO THE SOFTWARE HELP GUIDES FOR DETAILS
F
UNCTION
 
F
ACTORY
 
D
EFAULT
 
U
SER 
S
ELECTABLE 
C
HOICES
 
D
ESCRIPTION
 
High Transfer Point 
750TLV, 1000TLV  
and 1500TLV mod-
els:127AC    
 
750THV, 1000THV  
and 1500THV mod-
els:253VAC    
750TLV, 1000TLV  
and 1500TLV models:       
127, 130, 133, 136VAC 
 
750THV, 1000THV  
and 1500THV models:      
253, 257, 261, 265VAC 
If the utility voltage is usually high and the 
connected equipment is specified to operate 
with input voltages this high, set the high 
transfer point higher to avoid unnecessary 
battery usage. 
Low Transfer Point 
750TLV, 1000TLV  
and 1500TLV mod-
els:106VAC 
 
750THV, 1000THV  
and 1500THV mod-
els:208VAC 
 
750TLV, 1000TLV  
and 1500TLV models: 
97, 100, 103, 106VAC 
 
750THV, 1000THV  
and 1500THV models:      
196, 200, 204, 208VAC
 
If the utility voltage is usually low and the 
connected equipment is specified to operate 
with input voltages this low, set the low 
transfer point lower.