Minuteman UPS CPE 1000 ユーザーズマニュアル

ページ / 17
 
20
•  CAUTION – Replace batteries with the same number and type as 
originally installed in the UPS.  These batteries have pressure-operated 
vents.    These UPSs contain sealed non-spillable lead acid batteries. 
Model Number 
CPE 1000 
CPE 2000 
CPE 3000 
Battery 
QTY/Rating 
3-12V7.2Ah 6-12V7.2Ah 8-12V7.2Ah 
CSB 
Part Number 
GP1272 F2 
GP1272 F2 
GP1272 F2 
Panasonic 
Part Number 
LC-R127R2CH1 LC-R127R2CH1  LC-R127R2CH1 
Yuasa 
Part Number 
NP7-12 NP7-12  NP7-12 
 
5.5. Battery Replacement Procedure 
 
PLEASE READ THE CAUTIONS AND WARNINGS BEFORE 
ATTEMPTING TO REPLACE THE BATTERIES
 
 
•  CAUTION - DO NOT short-circuit any of the battery wires to the chassis 
or to any component. 
 
NOTE:    Do not pinch the battery wires with the battery-retaining brackets. 
 
NOTE:    It is recommended that you draw a diagram of battery position and 
the battery connections before disconnecting any of the battery wires. 
 
1.  Turn off the equipment that is plugged into the output receptacles of the 
UPS. 
2.  Press the On/Off switch on the front panel to turn the UPS OFF. 
3.  Unplug the UPS's Input power cord from the wall outlet. 
4.  Unplug the equipment from the output receptacles of the UPS. 
5.  Unplug the computer interface cable from the rear panel of the UPS. 
6.  Remove the cover screws. 
7.  Remove the cover. 
8.  Disconnect the battery positive (red) wire. 
NOTE:  Use CAUTION, do not touch the battery positive (red) wire to the 
battery negative (black) wire or the chassis. 
9.  Put a piece of electrical tape over the end of the battery positive (red) 
wire. 
10.  Press the On/Off switch on the front panel this will discharge the board. 
11.  Disconnect the battery negative (black) wire. 
12.  Disconnect the battery jumper wires. 
13.  Remove the battery-retaining bracket retaining screws. 
14.  Remove the battery-retaining bracket (s). 
15.  Remove the old batteries. 
16.  Install the new batteries. 
 
21
1
3
2
AC FUSE
17.  Re-install the battery-retaining bracket (s). 
18.  Re-install the battery-retaining bracket retaining screws. 
19.  Reconnect the battery jumper wires. 
20. Reconnect the battery negative (black) wire to the battery negative 
terminal.  Verify proper polarity. 
21. Remove the piece of electrical tape from the end of the battery positive 
(red) wire. 
22.  Reconnect the battery positive (red) wire.    Verify proper polarity. 
NOTE:    Some sparking may occur, this is normal. 
23.  Re-install the cover. 
24.  Re-install the cover screws. 
25.  Reconnect the computer interface cable to the rear panel of the UPS. 
26.  Plug the equipment into the output receptacles of the UPS. 
27.  Plug the UPS's Input power cord into the wall outlet. 
28.  Press the On/Off switch on the front panel to turn the UPS ON. 
29.  Turn on the equipment. 
30.  The UPS is now ready for normal operation. 
31. Dispose of the old batteries properly at an appropriate recycling facility 
or return them to the supplier in the packing material for the new 
batteries. 
 
CPE 1000