Toshiba 1500 Plus ユーザーズマニュアル

ページ / 31
TOSHIBA
MODEL NUMBER
UE1E1E006-5M
CAPACITY
600 VA  (0.42 kW)
Input
Input voltage
Single phase, 220 Vac, +10% to -30% (*)
Input  frequency
45 to 65 Hz
Input capacity
600VA
Input  power  factor
Approximate unity (0.95 to 1.0)
Battery
Battery rated voltage
60 Vdc
         Battery backup time when fully charged
12 min. at full load  (**)
with 0.7 power factor at77° F (25° C)
30 min. at half load (**)
 Recharge time
Maximum 24 hrs to 100% (90% recharge after 8 hrs) (***)
Type of batteries
Sealed  lead-acid
Output
Output  voltage
Single-phase, 220 volts
Output  voltage  regulation
Within +/- 3%, steady state
  Output  frequency
50/60 Hz +/- 0.5% in free-running mode (line sync range +/- 1Hz)
Output  voltage  waveform
Computer-grade sine wave with less than 3.0% total harmonic
distortion with linear load
Common  Mode
Less than 0.5V peak
Normal  Mode
Less than 10V peak
Rated load power factor
0.7 lagging (0.6 to 1.0)
Voltage transient characteristic
+/- 8% under 100% load step change
Rated output current (rms)
2.7A
Maximum output current (peak)
8.0A
Inverter  overload  capacity
150% for 30 seconds
Crest factor
3.0
Environment
Operating temperature
32 to 104° F (0 to 40° C), optimal  at 77° F (25° C)
Storage  temperature
-4 to 104° F (-20 to 40° C)
Operating  humidity
30 to 90%, no condensation
Altitude(****)
Less than 3000 ft (1000 m) above sea level
External dimensions
8.00W x 20.38D x 10.00H in (203W x 518D x 254H mm)
Net weight
58.8 lb (26.7 kg)
Acoustical noise
50 dB at max. output, measured 3.3 ft (1 m) from front panel
Efficiency (ac-dc-ac)
85%
Switches
Bypass switch
Automatic bypass is provided when the run switch is in the stop
position, if a fault occurs, or if an overload occurs (transfer time is
approximately 4 mS)
Interfaces
IBM 
(TM) 
AS/400
LAN  Manager
See section 6.0 for details.
Fault detect and input power loss
RS232 ASCII
Options
Software for unattended
computer  shutdown
Contact Toshiba for details on this option
External  battery  pack
Contact Toshiba for details on this option
(*)  Output capacity reduced when input voltage is between -15% and -30% of nominal.
(**)  Battery backup time may vary depending on the operating conditions including ambient temperature at the
installation site.
(***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is used
for battery backup.
(****)  Above 3000 ft (1000 m), output capacity reduced.
4 - 2
4.2
Plus Series Specifications (w/ isolation transformer)
4.0
Specifications