  Power Supply Wiring and Grounding 
Fig. 2.2.1 RS500 Power Supply Inputs  
 
The power supply input is connected as follows: 
1.
  + = DC (+) is connected to the positive (+) terminal if the power source is DC or to the 
(Hot) terminal if the power source is AC. 
2.
  - = DC (-) is connected to the negative (-) terminal if the power source is DC or to the 
(Neutral) terminal if the power source is AC. 
3.
  Surge Ground is used as the ground conductor for all surge and transient suppression 
circuitry internal to the RS500.  Surge Ground is connected directly to the safety ground 
terminal internally.  
 
NOTE: Since the Chassis Ground is connected to the equipment ground bus internally, HIPOT 
testing cannot be performed in the field. 
 
Surge Ground
DC(+) 
DC(-)
Safety Ground
Stud