Quick Start 
H3C S3100-SI Series Ethernet Switches 
Chapter 2  Installation 
Preparation
 
2-4 
Table 2-2 
Limits on harmful gas in the equipment room 
Gas 
Max content (mg/m³) 
SO
2
0.2 
H
2
0.006 
NH
3
0.05 
Cl
2
0.01 
 
2.2.3  Anti-interference Requirements 
A switch in use may be affected by the interference from outside 
the system by way of capacitance coupling, inductance coupling, 
electromagnetic radiation, public impedance (including the grounding 
system) coupling or conducting line (power line, signaling line and 
transmission line etc.). Therefore, you should pay attention to the 
following: 
z
 
If AC supply system is TN system, AC power socket should 
be a single-phase three-line power socket with Protection 
Earth (PE) so that the filter circuit on the equipment can 
effectively filter out the interference coming from the power 
supply system. 
z
 
Keep the switch far away from high-power radio transmitters, 
radars, and high-frequency heavy-current devices. 
z
 
Adopt electromagnetic shielding measure if necessary. For 
example, you can adopt shielded interface cable. 
z
 
Wire interface cables indoors. Do not wire cables outdoors 
in case that overvoltage and overcurrent damage the 
device.