HP (Hewlett-Packard) RPC-3A ユーザーズマニュアル
RPC SERIES OWNER’S MANUAL
DETAILED OPERATION AND CONFIGURATION
________________________________________________________________________________
DETAILED OPERATION AND CONFIGURATION
________________________________________________________________________________
21
Accessing Main Menu
Power on the RPC unit. The following
status menu appears:
status menu appears:
RPC-2 Series
(c) 1997 by BayTech
F2.07
(c) 1997 by BayTech
F2.07
Circuit Breaker : On
1) . . . OUTLET 1 : Off
2) . . . OUTLET 2 : Off
3) . . . OUTLET 3 : Off
4) . . . OUTLET 4 : Off
5) . . . OUTLET 5 : Off
6) . . . OUTLET 6 : Off
2) . . . OUTLET 2 : Off
3) . . . OUTLET 3 : Off
4) . . . OUTLET 4 : Off
5) . . . OUTLET 5 : Off
6) . . . OUTLET 6 : Off
RPC >
If the status menu fails to appear, ensure the
correct cables and adapters are being used
and they are connected properly. Also,
verify the serial communication parameters
are correctly configured.
correct cables and adapters are being used
and they are connected properly. Also,
verify the serial communication parameters
are correctly configured.
Controlling Receptacles
To set or change the status of receptacles,
enter one of the following commands: ON
n, OFF n, REBOOT n, where “n” is the
outlet number you want to command.
Entering an outlet number of “0” sends the
command to all outlets.
enter one of the following commands: ON
n, OFF n, REBOOT n, where “n” is the
outlet number you want to command.
Entering an outlet number of “0” sends the
command to all outlets.
Example:
To turn “On” Outlet 3, type ON 3 from the
RPC prompt (RPC >). The RPC responds:
RPC prompt (RPC >). The RPC responds:
Turn On Outlet 3 (Y/N)?
Responding “Y” for yes turns “On” Outlet 3.
Observe the status of Outlet 3 has changed
to “On” in the status menu:
Observe the status of Outlet 3 has changed
to “On” in the status menu: