Delta Electronics RTU-EN01 ユーザーズマニュアル

ページ / 52
Modbus TCP Remote I/O Communication Module RTU-EN01 
 
DVP-PLC Operation Manual 
10 
B R # 5 :   C O M 2   C o m m u n i c a t i o n   S e t t i n g s
 
Explanations: 
b0 ~ b3 
Interface Explanation 
Data 
Baud rate
(bps) 
Data 
Baud rate 
(bps) 
Data 
Baud rate
(bps) 
0x1 110 0x6 2,400 0xB 
57,600 
0x2 150 0x7 4,800 0xC 
115,200 
0x3 300 0x8 9,600   
 
0x4 600 0x9 
19,200  
 
Content 
COM2 
RS-485 
0x5 1,200 0xA 38,400   
 
b4 ~ b7 
 
b7 
b6 ~ b5 
b4 
Explanation 
Stop bit 
0: 1 Stop bit 
1: 2 Stop bits 
Parity bit 
00 : None parity bit 
01 : Odd parity bit 
11 : Even parity bit 
Data bit 
0 : 7 Data bits 
1 : 8 Data bits 
0000 (0) 
7-N-1 
0011 (3) 
8-O-1
1000 (8) 
7-N-2 
1011 (B) 
8-O-2
0001 (1) 
8-N-1 
0110 (6) 
7-E-1
1001 (9) 
8-N-2 
1110 (E) 
7-E-2
Content 
0010 (2) 
7-O-1 
0111 (7) 
8-E-1
1010 (A) 
7-O-2 
1111 (F) 
8-E-2
b8 ~ b15 
Content 
Explanation 
0x02 
Modbus RTU Master 
0x03 Modbus 
ASCII 
Master 
 
 
B R # 6 :   A d d r e s s
 
Explanations 
For filling in or reading the Modbus address. The address will be displayed in the message display after being set 
up. Range: 1 ~ 247. 
 
B R # 7 :   N u m b e r   o f   D I   P o i n ts
 
Explanations 
Read the number of digital input points from BR#7. Range: 0 ~ 256. Max. I/O points: 256. 
 
B R # 8 :   N u m b e r   o f   D O   P o i n ts
 
Explanations 
Read the number of digital output points from BR#8. Range: 0 ~ 256. Max. I/O points: 256. 
 
B R # 9 :   E r r o r   C o d e
 
Explanations: 
Error code = 0 refers to no error occurring. 
Code 
Indication 
How to correct