Siemens Module B3 ユーザーズマニュアル

ページ / 64
 
 
 
 
 
 
 
   
Automation and Drives - SCE 
 
 
 
 
T I A  Training Document 
Page 18 of 64 
  Module 
 
2.7 Types of Controllers 
 
2.7.1 Two Position Controllers 
 
  The essential feature of two position controllers consists of their knowing only two modes: “On“ and 
“Off“  -which makes them the simplest type of controller. Two-position controllers are used primarily 
when adhering to a setpoint exactly is less important than to keep the control system as simple as 
possible; or, when the actuator or the final control element does not allow for a continuous control 
system.  The heating system mentioned several times above is -with a control loop having a room 
thermometer and a mixer- a continuous control system.  To keep the water temperature in the boiler 
loop constant, typically a two position controller is used since it can, on the one hand, fluctuate by a 
few degrees, and on the other hand it is clearly simpler to switch the burner on and off than to do an 
exact dosing of fuel to be added.  
 
Since theoretically -to adhere to the setpoint exactly- it would be necessary to switch a system on 
and off infinitely fast, the two position controller has a so-called “hysteresis“.  It represents a kind of 
“environment“ around the setpoint within which the actual value may fluctuate. That means, we 
specify a minimum value that is lower than the setpoint, and a maximum value that is a little higher 
than the setpoint.  Only if the actual value exceeds the maximum value or drops below the minimum 
value does the control system react. In most cases, the minimum and the maximum value are 
distanced from the setpoint equally; that is, the hysteresis generates a symmetrical environment 
around the set point.   
In the case of the boiler water temperature, the burner would be switched on, for example, when the 
water temperature drops below the specified setpoint by more than a certain value. The burner 
continues to run until a certain value that is above the setpoint is exceeded. Only then will the burner 
be switched off.  Another typical example is cooling. Usually, a cooler also does not support a 
continuous control system, but only knows the states “On“ and “Off“. It is switched on when the 
actual temperature exceeds the setpoint temperature by a few degrees, and is switched off when the 
actual temperature is a few degrees too low.   
It is therefore typical for the two position controller to periodically fluctuate around the setpoint whose 
amplitude is roughly that of the hysteresis. The selection of the hysteresis depends on how exactly 
the setpoint has to be adhered to.  If we select a large hysteresis, the actual value can deviate more 
considerably from the setpoint.  If we select a smaller one, the setpoint is adhered to more exactly, 
but the system would have to switch more frequently. This again has its disadvantages, such as a 
higher wear of the switching devices, and the actuator or the final control element. 
Preface     Fundamentals     Discontinuous Action Controller     Controller Block (S)FB41     Setting the System     Appendix 
B3 
Issued: 02/2008                                                                                                                                     Control Engineering with STEP 7