Siemens Module B3 ユーザーズマニュアル

ページ / 64
 
 
 
 
 
 
 
   
Automation and Drives - SCE 
 
 
 
 
T I A  Training Document 
Page 22 of 64 
  Module 
 
2.7.3.1 Proportional Controllers (P-Controller) 
 
In the case of a P-controller, the controller output  y is always proportional  to the recorded system 
deviation (y ~ e). The result is that a P-controller responds to a system deviation without a delay, and 
generates a controller output only if there is a deviation e. 
The proportional pressure regulator sketched in the figure below compares the force FS of the 
setpoint spring with the force FB that pressure p2 generates on the spring-elastic metal bellows.  If 
the force is not in balance, the lever rotates around the pivot point D. The valve position 
ñ changes, and accordingly the pressure p2 to be controlled until a new power balance is 
established. The figure shows the behavior of the P-controller as a sudden system deviation occurs. 
The amplitude of the controller output step y depends on the extent of the system deviation e, and 
the amount of the proportional coefficient Kp:  To keep the system deviation low, a proportional 
factor has to be selected that is as large as possible. Increasing the factor accelerates the reaction 
of the controller;  however, a value that is too high may cause overshoot, and a considerable 
oscillatory tendency of the controller. 
 
 
 
 
 
Metal Bellows
 
 
 
 
Setpoint Spring 
 
 
 
 
 
 
 
 
Preface     Fundamentals     Discontinuous Action Controller     Controller Block (S)FB41     Setting the System     Appendix 
B3 
Issued: 02/2008                                                                                                                                     Control Engineering with STEP 7