SERVICE 
 
PARAMETERS 
 
DESCRIPTION OF PARAMETERS 
 
Parameter Description 
Default 
(BCF...) 
Default 
(BC...) 
min MAX 
POSITIVE QUICK COOLING 
P01 
Room SetPoint  in pos. quick cooling, Soft phase 
23°F 
23°F 
-22°F 
86°F 
P02 
SetPoint in pos. quick cooling, Hard 
-12°F 
-12°F 
-40°F 
86°F 
P03 
Needle SetPoint in pos. quick cooling , Soft phase 
37°F 
37°F 
-22°F 
86°F 
P04 
Needle SetPoint  in  Hard quick cooling 
68°F 
68°F 
-22°F 
86°F 
P05 
Positive quick cooling duration 
90min 
90min 
0min 
900min 
P06 
Hard phase duration expressed as % in relation to P05  
60% 
60% 
0% 
100% 
P07 
Room SetPoint in pos. storing 
36°F 
36°F 
-22°F 
86°F 
NEGATIVE QUICK COOLING 
N01 
Room SetPoint in neg, quick cooling   
-12°F 
-12°F 
-40°F 
86°F 
N02 
Needle SetPoint in neg. quick cooling   
0°F 
-0°F 
-22°F 
86°F 
N03 
Negative quick cooling duration   
240min 
240min 
0min 
900min 
N04 
Room SetPoint in neg. storing   
-7°F 
-7°F 
-40°F 
86°F 
ALARMS 
A01 
Temperature alarm hysteresis 
4°F 
4°F 
0°F 
18°F 
A02 
High temperature limit alarm in pos. storing in relation to P07 18°F  18°F  0°F  90°F 
A03 
Low temperature limit alarm in pos. storing in relation to P07 -17°F  -17°F -90°F 0°F 
A04 
High temperature limit alarm in neg. storing in relation to N04 18°F  18°F  0°F  90°F 
A05 
Low temperature limit alarm in neg. storing in relation to N04 -17°F  -17°F -90°F  0°F 
A06 
Temperature alarm delay fron storing or defrost start 
60min 
60min 
0min 
300min 
A07 
Temperature alarm delay 
30min 
30min 
0min 
300min 
A08 
Duration of the buzzer in the alarm mode 
1min 
1min 
0min 
240min 
DISPLAY 
D01 
Temperature unit of measurement (0 Celsius; 1 Fahrenheit) 
D02 
Room probe Offset  
0°F 
0°F 
-18°F 
18°F 
D03 
BackLight (0 on when pressing a key; 1 always on) 
D04 
Core probe offset 
0°F 
0°F 
-18°F 
18°F 
D05 
Under surface probe offset 
0°F 
0°F 
-18°F 
18°F 
D06 
Over surface probe offset 
0°F 
0°F 
-18°F 
18°F 
DEFROST 
S01 
Performs defrost on quick cooling start 
0 = No; 1 = Yes 
0 0 
S02 
End-of-defrost temperature 
46°F 
46°F 
14°F 
86°F 
S03 
Defrost max. duration 
15 min 
15 min 
1 min 
90 min 
S04 
Interval between defrosts in storing (0=excluded) 
0 hour 
0 hour 
18 hour 
S05 
Type of defrost: 
0= electrical or due to compressor stop 
1= hot gas 
2= air 
2 2 
S06 
Dripping time 
1 min 
1 min 
0 min 
90 min 
S07 
Compressor activation delay with hot gas defrost   
0 sec 
0 sec 
0 sec 
600 sec 
S08 
First defrost activation time from storing start   (0=excluded) 
90 min 
S09 
Ignores compressor protection delays in defrost   
S10 
Defrost type started through keyboard: 
0= electrical or due to compressor stop 
1= hot gas 
2= air 
2 0