Cable information
This section provides cabling information for installing the HP ProLiant DL380 G6 Carrier-Grade
Server.
Server.
NEBS chassis ground
This carrier-grade product is intended for use in both common bonding networks and isolated
bonding networks. The product is equipped with a NEBS-compliant chassis ground lug located on
the rear of the product.
bonding networks. The product is equipped with a NEBS-compliant chassis ground lug located on
the rear of the product.
The ground lug included with the product accepts wire gauges between 10 and 12 AWG.
Network cabling
Intra-building connections of the HP ProLiant DL-Series Carrier-Grade Servers require the use of
shielded cables grounded at both ends.
shielded cables grounded at both ends.
CAUTION:
The intra-building ports of the equipment are suitable for connection to intra-building
or unexposed wiring or cabling only. The intra-building ports of the equipment must not be
metallically connected to interfaces that connect to the Outside Plant (OSP) or its wiring. These
interfaces are designed for use as intra-building interfaces only (Type 2 or Type 4 ports, as described
in GR-1089-CORE, Issue 4) and require isolation from the exposed OSP cabling. The addition of
primary protectors is not sufficient protection to connect these interfaces metallically to OSP wiring.
metallically connected to interfaces that connect to the Outside Plant (OSP) or its wiring. These
interfaces are designed for use as intra-building interfaces only (Type 2 or Type 4 ports, as described
in GR-1089-CORE, Issue 4) and require isolation from the exposed OSP cabling. The addition of
primary protectors is not sufficient protection to connect these interfaces metallically to OSP wiring.