Maintenance Object Repair Procedures
Page 10-535
DS1-BD (DS1 Interface Circuit Pack)
10
One-Way Span Test (#1214)
This test is destructive.
2
FAIL
The far CSU Loopback Test was not set up properly. The DS1 Interface circuit
pack could not put the far-end CSU into loopback mode.
pack could not put the far-end CSU into loopback mode.
3
FAIL
The far CSU Loopback Test was not set up properly. The framed 3-in-24 test
pattern, generated by the DS1 Interface circuit pack and looped back through
the far-end CSU, could not be detected by the DS1 circuit pack.
pattern, generated by the DS1 Interface circuit pack and looped back through
the far-end CSU, could not be detected by the DS1 circuit pack.
1. Retry
t
est ds1-loop PCSS far-csu-loopback-test-begin
.
2. If the Far CSU Loopback test continues to fail with this error code, the
problem could be with the TN767E board, the far-end CSU equipment, or
somewhere in between. Run
somewhere in between. Run
test ds1-loop PCSS
cpe-loopback-jack-test-begin
to see if the CPE Loopback Jack test which
is closer to the TN767E board is successful. (If a CPE Loopback Jack
device is not being used, then run
device is not being used, then run
test ds1-loop PCSS
ds1/csu-loopback-tests
to see if these even closer loopback tests
succeed). If the closer loopback test fails, follow the maintenance strategy
associated with that loopback
associated with that loopback
PASS
The Far CSU Loopback test has successfully began executing. The test will
continue to run until the system technician enters
continue to run until the system technician enters
test ds1-loop PCSS
end-loopback/span-test
or the
release board PCSS
.
0
NO
BOARD
BOARD
The test could not relate the internal ID to the port (no board).
This could be due to incorrect translations, no board is inserted, an incorrect
board is inserted, or an insane board is inserted.
board is inserted, or an insane board is inserted.
1. Check to ensure that the board translations are correct. Use the
add ds1
PCSS
command to administer the DS1 interface if it is not already
administered.
2. If board was already administered correctly, check the error log to
determine if the board is hyperactive. If this is the case, the board is shut
down. Reseating the board will re-initialize the board.
down. Reseating the board will re-initialize the board.
3. If the board was found to be correctly inserted in step 1, issue the
busyout
board
command.
4. Issue the
reset board
command.
5. Issue the
release busy board
command.
6. Issue the
test board long
command.
This should re-establish the link between the internal ID and the port.
Table 10-178.
TEST #1213 Far CSU Loopback Test —
Continued
Error
Code
Code
Test
Result
Description/ Recommendation
Continued on next page