Maintenance Object Repair Procedures 
Page 10-1024
POWER (Battery & Battery Charger) for AC-Powered Systems 
10
5. Check the battery dates and replace the batteries if they are more than 
four years old or if a POWER alarm is present.
NOTE:
If any defective batteries are found, replace all of them. Batteries are 
ordered in sets of three and should be replaced as such.
6. If no defective batteries are found, replace the entire charger.
7. Close the cover and secure it with the screw.
8. Reconnect the cord and move the power switch to ON.
Hardware Error Log Entries and Test to Clear 
Values
a. Where P is an appropriate port network number determined via the Port 
field from the Alarm or Error Log.
System Technician-Demanded Tests: 
Descriptions and Error Codes
Always investigate tests in the order presented in the table below when 
inspecting errors in the system. By clearing error codes associated with the 
Battery & Battery Charger Query Test,
 for example, you may also clear errors 
1.
Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the 
appropriate test description and follow the recommended procedures.
Battery & Battery Charger Error Log Entries
Error 
Type
Aux 
Data
Associated Test
Alarm 
Level
On/Off 
Board
Test to Clear Value
0
1
0
Any
Any
Any
test environment P sh r 1
1
Any
Battery & Battery 
Charger Query Test 
(#5) (Error Code 8)
MINOR
ON
test environment P sh r 1
257
Any
Battery & Battery 
Charger Query Test 
(#5) (Error Code 4)
MINOR
ON
test environment P sh r 1
769
Any
Battery & Battery 
Charger Query Test 
(#5) (Error Code 2)
MINOR
ON
test environment P sh r 1
3840
1005 
or 1028
Battery & Battery 
Charger Query Test 
(#5)
ON
test environment P sh r 1