DEFINITY Enterprise Communications Server  Release 6
Maintenance for R6vs/si  
555-230-127   
Issue 1
August 1997
Maintenance Object Repair Procedures 
Page 10-1415
TONE-PT (Tone Generator) 
10
For a system with a TN768, TN780 or TN2182 Tone-Clock Circuit Pack
:
Notes:
a. Refer to XXX-BD (Common Port Circuit Pack) Maintenance documentation 
for descriptions of these tests.
b. Refer to TONE-BD (Tone-Clock Circuit Pack) section for descriptions of 
these tests.
c. Refer to TDM-CLK (TDM Bus Clock) section for descriptions of these tests.
d. This test only runs on the Standby Tone-Clock circuit pack in a Port 
Network with more than one Tone-Clock circuit pack (High or Critical 
Reliability Option). The circuit pack must be a TN780 code with firmware 
revision 2 or above, or a TN2182.
Tone Generator Transmission Test (#40)
The purpose of this test is to verify that the tone generation hardware on the 
tone-clock circuit pack is capable of generating a subset of system tones and a 
set of test tones. This test does not verify all system tones the tone generator 
produces during normal system operation.
The test is performed in two parts. For the first part, the Tone Generator is told to 
generate the touch-tone digits. The digits are received and checked by a Tone 
1.
D = Destructive; ND = Nondestructive
Order of Investigation
Short Test 
Sequence
Long Test 
Sequence
D/ND
1
SAKI Reset Test (#53) (a)
X
D
Clock Health Test (#46) (b)
X
X
ND
Control Channel Loop Around Test (#52) (a)
X
X
ND
Tone Generator Crosstalk Test (#90)
X
ND
Tone Generator Transmission Test (#40)
X
X
ND
Tone Generator Audit/Update Test (#41)
X
X
ND
TDM Bus Clock Circuit Status Inquiry Test (#148) (c)
X
X
ND
TDM Bus Clock Slip Inquiry Test (#149)(e)(c)
X
X
ND
TDM Bus Clock PPM Inquiry Test (#150) (c)
X
X
ND
TDM Bus Clock Parameter Update Test (#151) (c)
X
X
Board Type Check Test (#574) (c)
X
X
Standby Reference Health Check Test (#651) (c,d)
X