Lucent Technologies lucent ユーザーズマニュアル

ページ / 2392
DEFINITY Enterprise Communications Server  Release 6
Maintenance for R6vs/si  
555-230-127   
Issue 1
August 1997
Maintenance Commands and Trouble-Clearing Aids 
Page 8-44
disable test-number 
8
disable test-number
This command prohibits selected maintenance tests from running. To run a 
disabled test number, enter the 
enable test-number
 command.
display alarms
This command creates an Alarm Report. The user completes an option screen to 
select the parameters for the report.
The system creates the reports from the logs of the maintenance subsystem. The 
subsystem monitors the system hardware and logs problems as errors or alarms. 
The type of alarm indicates the impact of the problem, as defined below: 
Warning alarm
A minor interference which does not noticeably impair service.
Minor alarm
A problem which could disable a local area of the system and 
noticeably impair service. 
Major alarm
A problem which widely degrades the system and seriously 
impairs service. The system automatically calls INADS to report major alarms.
Resolved alarm
A problem which has been corrected, and the system is 
correctly functioning. The system stamps resolved alarms with the date and time 
the problem was corrected. The system handles any errors associated with the 
alarms as “resolved.”
1.
Refer to the Report Scheduler and System Printer feature specification for more details.
Action/Object
Qualifier
Qualifier Description
Permissions
Defaults
Feature
Interactions
disable 
test-number
number
print 
schedule
Maintenance test number
Report sent to printer
Command is validated and then a 
scheduling form displays to 
schedule execution of the 
command. The command is then 
placed in the command queue 
and is executed at the specified 
time. The information displayed 
by the command is sent to the 
system printer instead of the 
screen.
1
Examples:
disable test-number 710 
disable test-number 710 print
disable test-number 510 
schedule
init
inads
none
none