DEFINITY Enterprise Communications Server  Release 6
Maintenance for R6vs/si  
555-230-127   
Issue 1
August 1997
Maintenance Object Repair Procedures 
Page 10-274
CARR-POW (Carrier Port Power Unit) for DC-Powered Systems 
10
Power Unit Query Test (#127)
This test queries the Maintenance/Tape Processor in a Standard system PPN, the 
Duplication Interface circuit pack in a PPN for a High or Critical Reliability 
system, or the EPN Maintenance circuit pack in an EPN multicarrier cabinet 
system for the status of the pair of port carrier power units in the specified carrier. 
If both port carrier units are on and functioning, the test passes. If both are not on 
and functioning, the test fails.
1 (Carrier E)
2 (Carrier D)
4 (Carrier A)
8 (Carrier B)
16 (Carrier C)
FAIL
There is a problem with one or both port carrier power units on the 
recycled carrier.
1. Since the Power Unit Recycle Test failed, both port carrier power 
supplies in the recycled carrier should have been powered off by 
the system software. Both port carrier power units should be 
showing a red status LED, instead of a green one. Since the Power 
Unit Query Test is a subset of the Power Unit Recycle Test, the 
Power Unit Query Test (#127) should also fail. Run the Power Unit 
Query Test by using the 
test environment P
 command where P is 
the appropriate port network number.
2. If the test fails, follow the repair procedures described for Test 
#127. If the problem persists, follow normal escalation procedures.
PASS
Both port carrier power units in the recycled carrier were found to be 
healthy by the Maintenance/Tape Processor in Standard system PPN, 
the Duplication Interface circuit pack in a PPN for a High or Critical 
Reliability system, or the EPN Maintenance circuit pack in an EPN 
multicarrier cabinet system after the port carrier power units were 
powered-down and powered up again. If the status LEDs on both port 
carrier power units are not showing green, then the PR-MAINT 
(Maintenance/Tape Processor), DUPINT (Duplication Interface) circuit 
pack, or the EPN MAINT (Maintenance) circuit pack may have 
incorrectly reported the state of the port carrier power units. Look for 
and resolve any alarms on these MOs.
Table 10-89.
TEST #126 Power Unit Recycle Test  — 
Continued
Error Code
Test 
Result
Description/ Recommendation
Continued on next page