DEFINITY Enterprise Communications Server  Release 6
Maintenance for R6vs/si  
555-230-127   
Issue 1
August 1997
Initialization and Recovery 
Page 4-11
Procedure for Duplication Interface — Processing Element Communication Down 
4
Procedure for Duplication Interface 
Processing Element Communication 
Down
In a High or Critical Reliability system, it is possible for both SPEs to stop 
communicating with the A-carrier TN772 Duplication Interface (DUPINT-A) circuit 
pack. Thus, the DUPINT-A, which is in charge of maintenance, prints the 
following message on the administration terminal:
Duplication Interface-Processing Element Communication down
The system may continue to function on one of the SPEs. However, the system is 
not able to provide any interface to the administration terminal.
If the system is still providing service, connect the administration terminal to the 
Active SPE (check the amber LED on the Processor circuit pack). Then, if 
Table 4-1.
Order of Circuit Pack Replacement
Alarm
Suggested Circuit Packs
To Replace
PROC_BD
1) Processor
2) Network Control
MEM_BUS
1) Processor
2) Network Control
PROC_MEM
1) Processor
OFFBD_MEM
1) Processor
2) Network Control
INVALID_ERR
1) Processor
2) Network Control
MAINT_BD
1) Processor
2) Network Control
NETCON_ABSENT
1) Network Control
2) Processor
NO_CARTRIDGE
1) Memory Card
2) Network Control
3) Processor