Black Box LES1408A ユーザーズマニュアル

ページ / 286
 
 
7.2 
Check Conditions  
To configure the condition that will trigger the Auto-Response: 
  Click on the Check Condition type (e.g. EnvironmentalUPS Status or ICMP ping) to be 
configured as the trigger for this new Auto-Response in the Auto-Response Settings menu 
7.2.1   UPS / Power Supply   
To use the properties of any attached UPS as the trigger event:  
  Click on UPS / Power Supply  as the Check Condition  
  Select UPS Power Device Property (Input Voltage, Battery Charge %, Load %, Input 
Frequency Hz or Temperature in °C) that will checked for the trigger 
  Specify the Trigger value that the check measurement must exceed or drop below to trigger 
the AutoResponse  
  Select Comparison type as being Above Trigger Value or Below Trigger Value to trigger 
  Specify any Hysteresis factor that is to be applied to environmental measurements (e.g. if an 
Auto-Response was set up with a trigger event of a battery charge below 20% with a 
Hysteresis of 5 then the trigger condition would not be seen as having been resolved till the 
battery charge was above 25%)  
  Check Save Auto-Response 
 
Note:    Before configuring UPS checks in Auto-Response you first must configure the attached UPS  
7.2.2 
UPS Status   
To use the alert state of any attached UPS as the Auto-Response trigger event:  
  Click on UPS Status  as the Check Condition  
  Select the reported UPS State to trigger the Auto-Response (either On Battery or Low 
Battery)The Auto-Response will resolve when the UPS state returns to the "Online" state 
  Select which connected UPS Device to monitor  and check Save Auto-Response 
Note:    Before configuring UPS state checks in Auto-Response you first must configure the attached 
UPS  