Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
3
Introduction
Introduction
About this UPS
The APC Uninterruptible Power Supply (UPS) provides protection for electronic equipment from utility power
blackouts, brownouts, sags and surges. The UPS filters small utility line fluctuations and isolates electronic
equipment from large disturbances by internally disconnecting from utility line power. The UPS provides
continuous power from the internal battery until utility power returns to safe levels or the battery is fully
discharged.
Unpack
Read the Safety Guide before installing the UPS. The User Manual and Safety Guide are accessible on the
supplied User Manuals CD and on the APC Web site, www.apc.com.
Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage.
The packaging is recyclable; save it for reuse or dispose of it properly.
Check the package contents:
Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage.
The packaging is recyclable; save it for reuse or dispose of it properly.
Check the package contents:
Specifications
•
UPS
•
Front bezel
•
Rail kit
•
EPO connector
•
UPS literature kit containing:
–
–
Two mounting brackets
–
Eight flathead screws
–
Product documentation
–
Smart-UPS® User Manuals CD
–
PowerChute® CD
–
Serial and USB communication cables
–
Safety information
–
Warranty information
230V Models Only:
UPS literature kit additional contents:
•
Input power cord
•
Alternate input power cord
(UK customers)
•
Utility connector plug
•
IEC jumper cables
The model and serial numbers for all units are
located on the rear panel. See the small label
with numbers and bar codes.
Temperature
Operating
Storage
32
°
to 104
°
F (0
°
to 40
°
C)
5
°
to 86
°
F (-15
°
to 30
°
C) charge the UPS battery every six months
86
°
to 113
°
F (30
°
to 45
°
C) charge the UPS battery every three months
This unit is designed for indoor
use only. Select a location sturdy
enough to handle the weight.
Do not operate the UPS where
Do not operate the UPS where
there is excessive dust or the
temperature or humidity are
outside the specified limits.
outside the specified limits.
Maximum
Elevation
Operating
Storage
10,000 ft (3,000 m)
50,000 ft (15,240 m)
50,000 ft (15,240 m)
Humidity
0 to 95% relative humidity, non-condensing
Weight
135 lbs (61 kg) with battery module
80 lbs (36 kg) without battery module
80 lbs (36 kg) without battery module
135 lbs (61 kg)
Maximum Number of External Battery Packs Supported by the
Smart-UPS XL
10