Siemens TPS3 ユーザーズマニュアル

ページ / 16
Storage
The  unit  should  be  stored  in  a  clean,  dry  environment.  Storage
temperature is -55o C (-67o F) to +85o C (+185o F). Avoid exposing
the unit to areas of high condensation. All of the packaging materials
should be left intact until the unit is ready for installation. If the unit
has been stored for an extended period of time, it may be necessary
to clean the unit and make a complete inspection of the unit prior to
installing and placing into service.
Industry Standards Changes - 2009
UL 1449 Third Edition and 2008 NEC® Article 285 generated substantial
changes.
The term TVSS changed to SPD
Types 1, 2, 3 & 4 SPDs are created
UL 1449 clamping voltage performance testing changed from
500A to 3,000A
UL 1449 added new Nominal Discharge Current testing (I nominal,
or In), which consists of more rigorous duty-cycle testing
The SPD Type category is important to understand before installing
any SPD. Type 1 and 2 SPDs are fully UL Listed devices whereas Type
4 SPDs are UL Recognized devices.
Type  1  –  Installed  on  line  or  load  side  of  the  Main  Overcurrent
Protection (OCP), similar to obsolete products known as Secondary
Surge Arrestors, except now includes rigorous safety testing. Includes
all OCP & safety disconnectors inside the SPD.
Type 2 – Installed on load side of the Main OCP, similar to previous
products known as TVSS. May or may not require external OCP.
Type 3 – Point of Utilization, direct plug in type devices, surge strips,
etc. Theses devices are intended for installation 10 meters from the
panel (rationale based on IEEE Cat. A location).
Type 4 – Surge suppression components, could be a basic component
or a complete module. Type 4 components can be tested for Type 1,
Type 2 or Type 3 applications.
  
2008 NEC Art 285 & UL 1449-3
SPD Types: Types 1, 2, 3, & 4
Based on Location within electrical distribution system
(also coincides with ANSI/IEEE C62.41.2 - 2002 Categories C, B &A)
Figure 1: SPD Types
Siemens TPS3 SPDs have the following Type designations
Table 1: Type Designations
SIEMENS TPS3 SERIES
TYPE RATING
TPS3 01 & L1
Type 4 for Type 1 applications
TPS3 05 & L5
Type 1
TPS3 06 & L6
Type 4 for Type 1 applications
For further information, please review latest editions of NEC® Art. 285,
UL 1449, contact your local Siemens sales office or contact Siemens
TPS Tech Support at (888) 333-3545.
Equipment Performance
As SPDs sense overvoltage, they create a momentary internal short
circuit, thereby redirecting harmful surge energy to earth ground.
SPDs are capable of repeating this function repeatedly. For optimum
protection, staged surge suppression should be implemented at the
service entrance and all other distribution or panelboard locations
feeding sensitive equipment.
Voltage Rating
Prior to installing the TPS3 SPD, verify that the unit has the correct
voltage rating for the equipment installed by checking the nameplates
of both the equipment and TPS3 module. The service type should
match the intended power source. See Table 2 on the following page
for voltage applications.
2