Installation and Operation Manual 
Operation
LED Status Indicators
The diagnostic display panel shows the status of the SPD module with 
diagnostically controlled green/red LEDs. If a unit is operating correctly, all the 
phase LEDs will be illuminated green. To test the integrity of the diagnostics for 
each phase, push the button below the phase LEDs on the diagnostic display 
panel. The green LED will turn red and the alarm will sound, if the alarm is 
enabled. Releasing the test button will complete the test; the red LED will turn 
green and the alarm will shut off.
If an inoperable condition occurs on any phase, the audible alarm sounds and 
the corresponding phase LED on the diagnostic display panel is illuminated red. 
This indicates that the device needs service by qualified electrical personnel. 
The audible alarm can be silenced by pressing the alarm enable/disable button. 
The alarm will silence and the green alarm LED will not be lit. The red phase 
LED will continue to be illuminated until the inoperative condition had been 
cleared.
On an SurgeArrest
®
 
module (see Figure 6), if the left green LED is not lit, it 
indicates a loss of suppression from line-to-ground for that phase. If the right 
green LED is not lit, it indicates a loss of suppression from line-to-neutral for that 
phase. If the diagnostic display has power and both green LEDs are not lit the 
module should be replaced.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe 
electrical work practices. See NFPA 70E.
• This equipment must only be installed and serviced by qualified 
electrical personnel.
• Turn off
 
all power supplying this equipment before working on or inside 
equipment.
• Always use a properly rated voltage sensing device to confirm power is off.
• Replace all devices, doors and covers before turning on power to this 
equipment.
• This equipment must be effectively grounded per all applicable codes. 
Use an equipment-grounding conductor to connect this equipment to 
the power system ground.
Failure to follow these instructions will result in death or serious injury.
Figure 6:
SurgeArrest
®
 
Module LEDs
G
N
N
N
G
G
Left green LED lit:
L-G suppression is operating
Left green LED not lit:
Loss of surge suppression from L-G 
Right green LED lit:
L-N suppression is operating
Right green LED not lit:
Loss of surge suppression from L-N 
Operation