APC PMH3XS-B ユーザーズマニュアル

ページ / 24
20
Installation and Operation Manual 
Troubleshooting
If a module shows two green indicator lights and the display panel shows a red 
phase indicator light, follow the Troubleshooting Flow Chart in Figure 9 below.
Replacement Parts
The following replacement parts are available. For ordering information refer to 
the product catalog.
SPD modules. Replacement instructions are included with the 
replacement parts.
Diagnostic display panel assemblies. Replacement instructions are 
included with the replacement parts.
Figure 9:
Troubleshooting Flowchart
START
Red phase 
LED(s) lit.
Alarm on?
Is alarm 
Enable/Disable
LED on?
Press alarm 
Enable/Disable
switch. Is 
alarm on?
Is alarm LED 
on?
NO
NO
YES
YES
Check
patch cable
connections. Is
Red LED(s)
on?
Check the 
voltage on 
each phase.  Is 
the voltage 
correct?
LEDs lit on
all modules?
Possible diagnostic
display panel failure.
Contact APC 
Technical Support at
1-800-800-4272 for
troubleshooting. 
NO
YES
YES
YES
NO
YES
YES
NO
Check the power 
utility feed and 
verify voltage levels.
NO
Replace module(s) 
that do not have 
LEDs lit.
Energize SPD and 
verify proper
connection.
NO
Troubleshooting