Electrical
Voltage Rating
Prior to mounting the SPD, verify that the device has the same voltage rating as 
the power distribution system in which it is installed. Compare the nameplate 
voltage or model number on the SPD with the nameplate of the electrical 
distribution equipment.
The specifier or user of the device should be familiar with the configuration and 
arrangement of the power distribution system in which any SPD is to be 
installed. The system configuration of any power distribution system is based 
strictly on how the secondary windings of the transformer supplying the service 
entrance main or load are configured. This includes whether or not the 
transformer windings are referenced to earth via a grounding conductor. The 
system configuration is not based on how any specific load or equipment is 
connected to a particular power distribution system. See Table 2 for the service 
voltage of each SPD.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Confirm the SPD voltage rating on the module or nameplate label is the 
same as the operating voltage.
Failure to follow these instructions will result in death or serious injury.
Table 2:
Voltage Ratings
Service Voltage
Peak Surge Current 
Rating Per Phase
Catalog Number
1
1
Enclosures are rated 3R
120/240, 
1 phase, 2-3 wire
120 kA
PMP3X S-B
120/208Y, 127/220Y
3 phase, 3-4 wire 
120 kA
PMF3X S-B
240/120, 
3 phase, 4 wire (high-leg delta)
120 kA
PMJ3X S-B
277/480Y, 
3 phase, 3-4 wire 
120 kA
PMG3X S-B
220/380Y, 230/400Y, 240/415Y 
3 phase, 3-4 wire 
120 kA
PMH3X S-B
347/600Y, 
3 phase, 3-4 wire
120 kA
PML3X S-B