CAUTION
LOSS OF SURGE PROTECTION
·  During installation into an electrical system, SPD’s must not be energized until the electrical system 
 
  is completely installed, inspected, and tested. All conductors must be connected and functional,    
  including the neutral. The voltage rating of the device and system must always be verified before  
  energizing the surge protective device.
·  Any factory or on-site testing of power distribution equipment that exceeds the normal operating  
  voltage, such as high-potential insulation testing, or any other tests where the suppression  
  components will be subjected to voltages higher than their rated turn-on voltage must be performed  
  with the suppressor disconnected from the power source. The neutral connection at the SPD must  
  also be disconnected prior to performing high-potential testing and then reconnected upon  
  completion of the test.
Failure to follow these instructions can result in loss of power or loss of surge protection 
that can cause injury or equipment damage.
 
 
personnel.  No responsibility is assumed by APC for any consequences arising out of the use of
Electrical equipment should be installed, operated, serviced, and maintained only by qualified
 
this material.
 
IMPORTANT!
3
WARNINGS
APC MODULAR PANEL PRODUCTS Surge Protective Device (SPD)