Schneider Electric SR2MAN01 ユーザーズマニュアル
Sample Application
182
SR2MAN01 11/2007
Configuring the
Function Blocks
Function Blocks
The table below provides details on the parameters to use for each of the function
blocks:
blocks:
Function block
Comment
Counter function block
C1
The preset value is 93 (the
maximum number of vehicles
allowed in this car park).
Where necessary, this value may
be changed during operation.
maximum number of vehicles
allowed in this car park).
Where necessary, this value may
be changed during operation.
Clock function block
H1
Open hours:
z
Monday to Friday from 8:30 am
to 5:30 pm.
to 5:30 pm.
z
Saturdays from 9:30 am to
12:00 noon.
12:00 noon.
z
Closed all day Sundays.
Two ranges are used.
Timer function block
T1
Car park lighting timer: 10 minutes.
R C 1
D C T : T O P = 0 0 0 9 3
Menu / OK
-
+
C C 1
C 1
t
Menu / OK
-
+
H 1 D / W 0 1 2 3 4 _ _
C
H : M O N 0 8 : 3 0
H : M O F F 1 7: 3 0
Menu / OK
-
+
H 1 D / W _ _ _ _ _ 5 _
C
H : M O N 0 9 : 3 0
H : M O F F 1 2 : 0 0
Menu / OK
-
+
T T 1
R T 1 M : S
T 1
t = 1 0 . 0 0
B
t