Chapter 6 Fault Code Information|VFD-S Series 
6-4
 
Revision August 2006, SE08, SW V2.61
 
Fault 
Name 
Fault Descriptions 
Corrective Actions 
 
Communication Error 
1. 
Check the RS485 connection between the AC 
motor drive and RS485 master for loose wires 
and wiring to correct pins. 
2. 
Check if the communication protocol, address, 
transmission speed, etc. are properly set. 
3. 
Use the correct checksum calculation. 
4. 
Please refer to group 9 in the chapter 5 for 
detail information. 
  Software protection failure 
Return to the factory. 
  Password is locked. 
Keypad will be locked. Turn the power ON after 
power OFF to re-enter the correct password. See 
Pr.0-07 and 0-08. 
 
Analog feedback error or 
ACI open circuit 
1.  Check parameter setting (Pr.A-00) and 
AVI/ACI wiring 
2.  Check for possible fault between system 
response time and the feedback signal 
detection time (Pr.A-08). 
 
Phase Loss 
Check input phase wiring for loose contacts. 
 
PID feedback error 
1. 
Check PID feedback wiring. 
2. 
Check if the parameter setting is properly set.
6.2 Reset 
There are three methods to reset the AC motor drive after solving the fault: 
1. Press 
STOP/RESET
 key on keypad. 
2. 
Set external terminal to “RESET” (set one of Pr.4-04~Pr.4-08 to 06) and then set to be 
ON. 
3. 
Send “RESET” command by communication. 
NOTE
  
Make sure that RUN command or signal is OFF before executing RESET to prevent damage or 
personal injury due to immediate operation.