Lincoln 1100 Series ユーザーズマニュアル

ページ / 92
No main fan cool down
20 Minute Time Delay
Check for 120 VAC at pin#2 and #3
Relay
while main fan is running.  Turn off
main fan switch and 120 VAC should
continue to be present for 20 minutes.
Main Fan Relay
Check if relay is operating and
terminals are remaining closed for
main fan cool down of 20 minutes.
Main fan runs after
NOTE: The time delay relay will
20 minute cool down
keep the coil of the main fan relay
closed, maintaining main fan operation for
cool down for approximately 20 minutes.
Cool Down Relay
Contacts of the relay should
open when main fan is switched off.
Time Delay
120 VAC at terminal 2 should
discontinue approximately 20 minutes after main
fan is switched off.  If cool down relay is open and
voltage continues at terminal 2,
replace time delay.
Main Fan Relay
When voltage at terminal 2 of time
delay ceases, main fan relay must open.
No control box cooling
Incoming Power
Check main circuit breakers, reset if
required, call power company if
needed.
Main Fan Switch
Check continuity between switch
terminals.
Control Box High Limit
Terminals are normally closed, and
Thermostat
open at 170°F ± 5°F (76.6°C ± 2.8°C).
Note: Discontinued at
Check for over heating and reset
S/N 2011821
thermostat.  Test for proper operation.
If it will not reset and hold, replace.
Fuse, 1 Amp
Check, replace if necessary.
Fuseholder
Check, replace if necessary.
Step Down Transformer
120 VAC should be present on
secondary.  Replace as needed.
Cooling Fans
120 VAC should now be at these fan
motors.  If voltage is present, check
motors for shorts or opens.
WITH POWER OFF: Check for locked rotor.
No automatic control
Incoming Power Supply
Check circuit breakers, reset if
box cooling
required, call power company if needed
Cooling Fan Thermostat Thermostat is normally
open and closes at 120°F ± 3 (48.9°C ± 1.7°),
and opens at 100°F ± 3°F
(37.8°C ± 1.7°C).
Control Box Hi Limit
Terminals are normally closed, but
Discontinued at S/N
open at 170°C ± 5°F (76.6°C ± 2.8°C).
2011821
Check for over heating and reset
thermostat.  Test for proper operation.
If it will not reset and hold, then
replace.
Fuse, 1 Amp
Check, replace if necessary.
Fuseholder
Check, replace if necessary.
Step Down Transformer
120 VAC ± 10%  should be present at
secondary of transformer.  If proper
voltage is not present, check
transformer primary for proper
input.  Replace as needed.
Impinger II - 1100 Series Service Manual - International